Inspection History Details
Inspection Status: Approved
Inspection History: SIGN SHOP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/06/2006 | SIGN SHOP | Approved | IVRS - Inspection :* | |
| 05/02/2006 | SIGN SHOP | Not ready for Inspection | IVRS - Inspection :* 1. GLASS TO SPRING IN ELECTRODE HOUSE TO USE APPROVED TERMINATIONS - ALSO TIGHTEN TERMINAL SCREWS. 2. REVISE PLANS FOR ELECTRODE HOUSING FROM DOUBLE BACK CONNECTIONS. |
|
| 04/28/2006 | SIGN SHOP | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. ALL BOXES NEED TO BE GROUNDED. 2. SIGN CKT NOT CORRECTLY IDENTIFIED IN PANEL. 3. MOUNT J-BOX TO ENCLOSURE AND TIGHTEN LOCKNUTS. |