| 05/25/2006 | SIGN SHOP | Approved | IVRS - Inspection :* | |
| 04/25/2006 | SIGN SHOP | Partial Approval | IVRS - Inspection :* 1. A MARKING LABEL IS NEEDED 600.4 2. SWITCH TO BE CAPABLE OF BEING LOCKED OUT 600.6 3. SUPPORT M/C CABLE FROM SIGN JUNCTION BOX 4. FINISH INSTALLATION. |