Inspection History Details
Inspection Status: Denied
Inspection History: SIGN ELECTRIC
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/18/2007 | SIGN ELECTRIC | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 05/18/2007 | SIGN ELECTRIC | Approved | IVRS - Inspection :* RECEIVED CHECK/MONEY ORDER #602845641 $108.00 |
|
| 05/06/2007 | SIGN ELECTRIC | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 04/26/2007 | SIGN ELECTRIC | Denied | 1. WHEN PVC CONDUIT IS USED ABOVE GROUND IT MUST BE SCHEDULE 80 - STRONGER THAN 40 2. CANNOT BURY AN LB FITTING WHERE TRENCH TURN TO SERVICE. 3. CONDUIT TO BE 18" DEEP -- CHECK AT WHERE IT TURNS TO SERVICE APPEARS 12-14" ONLY 4. BOX IN WALLED AREA BELOW SIGN LOOSE 5. A WHITE WIRE CANNOT BE TAPED GREEN AND USED AS A GROUND. 6. J-BOX IN WALLED AREA TO LOW CANNOT BE BURIED. |