Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/25/2008 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 12/19/2007 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* NOTE CORRECTIONS LISTED BELOW (INSP. 5/23/07) |
|
| 05/23/2006 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* SECTION 1004 OF IBC REQUIRES THAT INCREASE OF OCC. LOAD IS PERMITTED ONLY IF OTHER CODE REQUIREMENTS MET OF 1007 IBC. 1. 1993 WATER HEATER INSTALLED WITHOUT PERMIT - TPRV DISCHARGE TRAPPED AND NOT RUN TO APPROVED LOCATION. 2. BAR SINK IN UTILITY ROOM NOT INSTALLED PER PLUMBING CODE OR WITH PERMIT. 3. ILLUMINATED EXIT SIGNS REQUIRED AT 5 EACH INDICATED EXITS. 4. EMERGENCY EGRESS LIGHTING REQUIRED. 5. ACCESSIBLE ROUTE PER CHAP. 11 REQUIRED TO ALL COMMON AREAS. 6. PROPERLY TERMINATE ALL ELECTRICAL (KITCHEN) THAT IS NOT BEING USED. 7. ALL HOSE BIBBS REQUIRE ATMOSPHERIC VACUUM BREAKERS. 8. EMERGENCY EGRESS LIGHTING REQUIRED PER CHAPER 10 IBC 9. WATERPROOF COVERS REQUIRED AT EXTERIOR PLUG, RECEPTACLES. 10. OVERFLOW @ EVAP. COOLER ON ROOF TRAPPED. 11. GATE EXITING REAR YARD BLOCKED. 12. EXITING THROUGH INTERVENING SPACES IS ONLY ALLOWED PER SECTION 1013 OF IBC. IT MAY BE ALLOWED BY BUILDING OFFICIAL WITH PROPER EXIT ILLUMINATION AND SIGNAGE. |
|
| 05/19/2006 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* I NEED APPROVED PLANS AND PERMITS @ SITE |
|
| 05/04/2006 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* - PROVIDE C.O.T APPROVED FLOOR PLAN - REQUIRES RECENT APPROVAL |