Inspection History Details
Permit: T06OT00552
Inspection Status: Approved
Inspection History: SIGN ELECTRIC
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/20/2006 | SIGN ELECTRIC | Approved | IVRS - Inspection :* OK SIGN |
|
| 04/17/2006 | SIGN ELECTRIC | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. WHITE CANNOT BE USED AS OTHER THAN NEUTRAL/GROUNDED CONDUCTOR NOT STRIPED OUT AS GROUNDING. 2. COMPLETE ITEMS 1-5 PREVIOUS INSPECTION. |
|
| 03/27/2006 | SIGN ELECTRIC | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. SUPPORT CONDUIT INDEPENDENTLY AS PER 300.11 ALSO FLEX CONDUIT. 2. SUPPORT JUNCTION BOX 3. BOND JUNCTION BOX 4. FILL UNUSED OPENINGS 5. #1 PREVIOUS INSPECTION. CANNOT PAINT CONDUCTORS 6. PLEASE VERIFY L-11 LICENSED ELECTRICAL CONTRACTOR. |
|
| 03/09/2006 | SIGN ELECTRIC | Not ready for Inspection | IVRS - Inspection :* 1. GROUNDING EQUIPMENT CONDUCTOR TO BE GREEN ENTIRE LENGTH 250.119 2. PLEASE VERIFY SIGN CIRCUIT IS AS PER 600.5 |
|
| 03/08/2006 | SIGN ELECTRIC | Not ready for Inspection | IVRS - Inspection :* | |
| 03/06/2006 | SIGN ELECTRIC | Not ready for Inspection | IVRS - Inspection :* 1) OK SHOP |