Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: CERTIFICATE OF OCCUPANCY
Permit Number - T06OT00437
Inspection Description - CERTIFICATE OF OCCUPANCY
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/08/2006 | CERTIFICATE OF OCCUPANCY | Approved | IVRS - Inspection :* | |
02/21/2006 | CERTIFICATE OF OCCUPANCY | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. CONNECT BACKFLOW DEVICES TO SODA AND ICE MACHINES 2. ATMOSPHERE VACUUM BREAKERS REQUIRED ON HOSE BIBS -- NOT PLASTIC CAPS |
|
02/16/2006 | CERTIFICATE OF OCCUPANCY | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. AVB REG. ON EXTERIOR HOSE BIBS & HOSE BIBS IN GARAGE 2. COVER EXTERIOR PLUG RECEPTACLES. 3. STOP LEAKS FROM COOLER AND HOSE BIBS 4. PROVIDE BACKFLOW CERTIFICATION 5. SUPPORT CM PIPE EVERY 6' 6. YOUR PLAN HAS SEPARATE MENS & WOMENS RESTROOMS WITH EXITS TO OUTSIDE. YOU WILL REQUIRE A T.I PERMIT TO BLOCK MENS ROOM DOOR, DEMO INTERIOR WALL, DOME TOILET, SINK, ETC AND TURN ROOM INTO STORAGE. 7. YOU REQUIRE A REVERSE PRESSURE BACKFLOW DEVICE FOR SODA MACHINE, CARBONATOR AND WATER SUPPLY. |
|
02/15/2006 | CERTIFICATE OF OCCUPANCY | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NO PLANS/PERMIT ON SITE 2) DOOR LOCKED-NO ACCESS |