Inspection History Details
Inspection Status: Partial Approval
Inspection History: SIGN SHOP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/22/2009 | SIGN SHOP | Partial Approval | IVRS - Inspection :* DRIVE ARROWS: 1) NEED SWITCHES AND LOCKOUTS FOR LED DRIVER 2) NEED WALK WAY TO LED POWER SUPPLIES 3) VERIFY LED POWER SUPPLIES IN ? MANUAL 4) FILL UNUSED OPENINGS NORTH LOGO: 1) ISOLATE POWER TO SWITCH SW LOGO: 1) PROTECT GTO AT PASS THRUS 2) PLANS NOT ON SITE FOR WORK INSTALLED-APPROVED PLANS |
|
| 04/05/2006 | SIGN SHOP | Partial Approval | IVRS - Inspection :* 1. ISOLATE POWER TO SWITCH. 2. REPLACE SMASHED & CUT CONDUCTORS 3. NEED TO INSPECT LED DRIVERS 4. SHEETMETAL SCREWS NOT ALLOWED FOR GROUNDING. |