Permit: T06OT00126

Parcel: 11445262J

Inspection Status: Not ready for Inspection

Inspection History: SIGN SHOP

Date Description Inspector Results Comments
11/02/2006 SIGN SHOP Not ready for Inspection IVRS - Inspection :*
1) ISOLATE POWER TO SWITCH AS STAMPED ON PLANS
2) PROTECT CONDUCTOR AT JUNCTION BOX
3) CANNOT FULLY OPEN COVER-RACEWAY TO BE ACCESSIBLE
4) CHECK GROUNDING NEXT INSPECTION-BOTH RACEWAY AND JUNCTION BOX
5) DO NOT ENERGIZE SIGN UNTIL FINALED BY ELECTRICAL INSPECTOR