Inspection Status: Approved
Inspection History: SIGN ELECTRIC
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/26/2006 | SIGN ELECTRIC | Approved | IVRS - Inspection :* OK SIGN |
|
| 05/19/2006 | SIGN ELECTRIC | Denied | IVRS - Inspection : See detailed listing on site.| 999* NO FURTHER INSPECTIONS UNTIL LICENSED ELECTRICAL (L-11) CONTRACTOR CONTACTS INSPECTOR. MY #909-4749 |
|
| 05/02/2006 | SIGN ELECTRIC | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NO MORE THAN 360 DEGRESS IN CONDUIT RUNS. 2. PROPERLY ANCHOR CONDUITS AND SEAL TITE. 3. DISCONNECT NOT MADE UP CORRECTLY - FILL UNUSED OPENINGS, USE CORRECT CONDUCTOR COLORS, DISCONNECT PROPERLY. 4. MAINTAIN WORKING CLEARANCE IN FRONT OF DISCONNECT. 5. FITTINGS TO BE LISTED FOR WET LOCATION. 6. CONDUCTOR TO BE ENCLOSED IN FULL RACEWAY SYSTEM. 7. FILL UNUSED OPENINGS IN PANEL. 8. BREAKERS TO BE LISTED FOR USE BY MANUFACTURER. 9. PLEASE VERIFY LICENSED L-11 ELECTRICAL CONTRACTOR PERFORMING WORK. 10. GROUND JUNCTION BOX. |
|
| 04/20/2006 | SIGN ELECTRIC | Not ready for Inspection | IVRS - Inspection :* |