Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/18/2006 | PLUMBING - FINAL | Approved | IVRS - Inspection :* 1. CORRECTIONS MADE OK 2. OK FOR C OF O S.T.O.I |
|
| 04/24/2006 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 04/21/2006 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. BESIDES ALL OF THE CORRECTIONS ABOVE - LESS THAN 50% COMPLETED - ABS DRAIN FROM ROOF NOT APPROVED. VENTS TO BE PAINTED WITH LATEX PAINT. 2. CONTINUED "NOT READY" MAY RESULT IN A RE-INSPECTION FEE. I ADVISE YOU TO HIRE A PLUMBER WHO IS FAMILIAR WITH COMMERICAL KITCHENS. |
|
| 01/06/2006 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) HOSE BIBS REQUIRES ATMOSPHERIC VACUUM BREAKERS 2) ALL WATER SUPPLIED APPLIANCES REQUIRE BACKFLOW PROTECTION. ICEMAKER REQUIRES WALLS 007 OR EQUAL 3) INDIRECT WASTE PIPING TO BE OF APPROVED MATERIAL, SUPPORTED, AND WITH CORRECT AIR GAP AT INDIRECT WASTE RECEPTACLE 4) WHEELED GAS APPLIANCES REQUIRE CABLE RESTRAINT AND QUICK DISCONNECT 5) RESTROOMS LACKING ADA REQUIREMENTS-SEE BLDG INSP. NOTES |