Inspection History Details
Inspection Status: Denied
Inspection History: SIGN SHOP
Permit Number - T06OT00008
Inspection Description - SIGN SHOP
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/16/2010 | SIGN SHOP | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEED MARKING LABEL 600.4 2) NEED WORK WAY TO ACCESS POWER SUPPLIES 600.21 3) NEED SERVICE LIGHT 210.70 4) FILL UNUSED OPENINGS IN BOXES 5) SUPPORT CONDUIT FALLING FROM STRUCTURE AND SUPPORT BOXES 6) TIGHTEN HIGH VOLTAGE CONNECTIONS AT 200 HOUSING |