Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/15/2007 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* CORRECTIONS HAVE BEEN MADE |
|
| 02/13/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : There is no access to the site.| 920* DOORS LOCKED. SCHEDULE WHEN SOMEONE WILL BE HERE. |
|
| 02/09/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. YOU CANNOT USE SINGLE WALL VENT PIPE OUTDOORS. PROVIDE DOUBLE WALL PIPE FROM THE T-WYE IN ATTIC TO 2' ABOVE ROOF. 2. VENT ON CONDENSATE MUST BE DOWNSTREAM OF THE TRAP. |
|
| 02/06/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) REPLACE OR REPAIR DBL WALL VENT PIPE 2) PROVIDE 1" CLEARANCE FROM WOOD AND WIRES 3) CONNECT LAV VOLTAGE TO CONDENSOR 4) PROVIDE A TRAP ON THE CONDENSATE DRAIN VENT TERMINATION ON ROOF MUST BE MINIMUM 12" ABOVE 5) OK TO REPAIR SHEETROCK |
|
| 01/10/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. GLUE THE SEAM ON REFER LINE INSULATION THE ENTIRE LENGTH OR REPLACE CUT INSTALLATION. 2. CONTROL WIRE MUST BE PROTECTED. 3. CONDENSOR MUST BE MIN. 12" AWAY FROM WALL. 4. COPPER CANNOT CONTACT STEEL. 5. DO NOT USE FLEX COPPER FOR REFRIGERATION PIPE. 6. INSULATE ALL SUCTION LINE PIPING. 7. DOUBLE WALL VENT ON FURNACE IS BROKEN. 8. RECONNECT SINGLE WALL VENT CONNECTOR & USE MIN. 3 SCREWS IN EACH JOINT. SUPPORT AS NEEDED. 9. INSULATE ALL A/C DUCT WORK 10. PROVIDE ROOF JACKS AT ROOF PENETRATIONS. 11. SUPPORT REFER LINES ON ROOF. 12. PROVIDE A CONDENSATE DRAIN. |