Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/15/2007 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* 1) PLEASE IDENTIFY THE NEUTRAL WIRE IN THE PANEL AND DISCONNECT 2) THE NEUTRAL MUST BE A WHITE WIRE |
|
| 05/01/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE AN OVERFLOW SENSOR ON SECONDARY DRAINS 2. I.D CIRCUIT BREAKER 3. SECURE THE ELEC. CONDUIT FROM THE DISCONNECT TO THE CONDENSOR 4. CONDENSATE CANNOT TERMINATE INTO A SEWER VENT 5. PROVIDE A GFI SERVICE RECEPTACLE WITH A WATERPROOF COVER ON ROOFTOP NEAR CONDENSOR. |