Permit: T06ME00745

Parcel: 133123070

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
06/15/2007 MECHANICAL - FINAL Approved IVRS - Inspection :*
1) PLEASE IDENTIFY THE NEUTRAL WIRE IN THE PANEL AND DISCONNECT
2) THE NEUTRAL MUST BE A WHITE WIRE
05/01/2007 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROVIDE AN OVERFLOW SENSOR ON SECONDARY DRAINS
2. I.D CIRCUIT BREAKER
3. SECURE THE ELEC. CONDUIT FROM THE DISCONNECT TO THE CONDENSOR
4. CONDENSATE CANNOT TERMINATE INTO A SEWER VENT
5. PROVIDE A GFI SERVICE RECEPTACLE WITH A WATERPROOF COVER ON ROOFTOP NEAR CONDENSOR.