Permit: T06ME00743

Parcel: 123060740


Addresses:

2111 E ADAMS ST

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
02/02/2007 MECHANICAL - FINAL Approved IVRS - Inspection :*
1) CORRECTIONS HAVE BEEN MADE
01/10/2007 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
MARK THE LOWER SECTION OF THE DATA PLATE WITH THE PROPER HEAT STRIP INSTALLED & FUSE ACCORDINGLY
30 AMP. FUSES TOO LARGE FOR THE HEAT STRIP.
25 AMP IS MAX.
IDENTIFY WHICH FUSE BANK IS FOR THE HEAT STRIP.