Permit: T06ME00737

Parcel: 11703284B


Addresses:

131 E 4TH ST


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T06ME00737

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/31/2007 MECHANICAL - FINAL Approved IVRS - Inspection :*
12/29/2006 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) CONDENSOR STILL OVERFUSED
2) 25 AMP IS MAX. FUSE SIZE
12/20/2006 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
PROVIDE CATWALKS & SERVICE PLATFORMS AS PER I.M.C
TERMINATE SECONDARY CONDENSATE TO A CONSPICUOUS LOCATION.
VENT MUST BE DOWNSTREAM OF THE TRAP
PROVIDE MIN. 1/8" PER FT. SLOPE ON DRAINS
SUPPORT HORIZONTAL SECTIONS EVERY 4'
FINISH INSULATING REFER LINES
DO NOT USE NYLON BANDS TO SUPPORT ANYTHING
USE SHEET METAL STRAPS OR OTHER APPROVED METHODS
ATTACH SUPPORTS TO STRUCTURE
DO NOT USE COPPER PLUMBERS TAPE TO SUPPORT FAN COILS
USE STEEL STRAP - NO PLUMBER TAPE
REFER LINES UNDERGROUND MUST BE MIN. 12" DEEP
SECURE ALL SEAMS ON REFER LINE INSULATION
USE GLUE
CONDENSORS OVERFUSED