Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/31/2007 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 12/29/2006 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CONDENSOR STILL OVERFUSED 2) 25 AMP IS MAX. FUSE SIZE |
|
| 12/20/2006 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* PROVIDE CATWALKS & SERVICE PLATFORMS AS PER I.M.C TERMINATE SECONDARY CONDENSATE TO A CONSPICUOUS LOCATION. VENT MUST BE DOWNSTREAM OF THE TRAP PROVIDE MIN. 1/8" PER FT. SLOPE ON DRAINS SUPPORT HORIZONTAL SECTIONS EVERY 4' FINISH INSULATING REFER LINES DO NOT USE NYLON BANDS TO SUPPORT ANYTHING USE SHEET METAL STRAPS OR OTHER APPROVED METHODS ATTACH SUPPORTS TO STRUCTURE DO NOT USE COPPER PLUMBERS TAPE TO SUPPORT FAN COILS USE STEEL STRAP - NO PLUMBER TAPE REFER LINES UNDERGROUND MUST BE MIN. 12" DEEP SECURE ALL SEAMS ON REFER LINE INSULATION USE GLUE CONDENSORS OVERFUSED |