Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/26/2007 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* CORRECTIONS HAVE BEEN MADE |
|
| 01/18/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SCRATCH OFF THE BOX ON THE DATA PLATE NEXT TO THE PROPER HEAT STRIP INSTALLED & FUSE ACCORDINGLY. USE THE BOTTOM SECTION OF DATA PLATE FOR SEPARATE POWER SUPPLY. 30 AMP FUSES TOO LARGE FOR 3.6/4.8 FW HEAT STRIP. 2. CONDENSATE CANNOT TERMINATE ONTO A SIDEWALK |