Permit: T06ME00716

Parcel: 112073210

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
03/26/2007 MECHANICAL - FINAL Approved IVRS - Inspection :*
03/22/2007 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) GAS TEST AT ZERO POUNDS
01/02/2007 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROVIDE AN 1/8" PER FT. SLOPE ON CONDENSATE DRAIN
2. DO NOT MOUNT DISCONNECT ON A SERVICE ACCESS PANEL
3. BLOCK & CLAMP GAS LINE ON ROOF
4. PROVIDE A SEDIMENT TRAP AT FURNACE
5. PROVIDE A TEST ON ALL NEW GAS PIPING