Inspection History Details
Permit: T06ME00694
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/04/2006 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* CORRECTIONS HAVE BEEN MADE |
|
| 11/29/2006 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 11/21/2006 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* - 9 PSI TEST IS NOT HOLDING - BLOCK & CLAMP PVC EVERY 4' - LOW VOLTAGE WIRE MUST BE PROTECTED. USE CONDUIT. - BLOCK & CLAMP ELEC. CONDUIT. SECURE WITHIN 12" OF CONNECTIONS. - DISCONNECT IS OVERFUSED. - BLOCK & CLAMP THE GAS LINE. |