Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/21/2006 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* CORRECTIONS HAVE BEEN MADE T06PL02022 03090 APPROVED LEFT GAS CARD |
|
| 11/17/2006 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* - PROVIDE DOUBLE WALL VENT PIPE WITH AN APPROVED CAP. - PROVIDE A TRAP ON CONDENSATE DRAIN LINE. - PROVIDE A GASKETED, SELF CLOSING DOOR ON FURNACE CLOSET. - PROVIDE A DISCONNECTING MEANS FOR FURNACE. - CONDENSOR OVERFUSED. - PROVIDE CONDUIT FOR CONDENSOR WIRE. |