Permit: T06ME00625

Parcel: 141140510


Addresses:

9640 E BANBRIDGE ST

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
05/04/2007 MECHANICAL - FINAL Approved IVRS - Inspection :*
CORRECTIONS HAVE BEEN MADE
04/30/2007 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. REMOVE & REPLACE FLATTENED CONDENSATE TRAP.
PROVIDE AN OVERFLOW SENSOR ON SECONDARY DRAIN.
2. INSULATE BARE SHEETMETAL SLEEVE ABOVE COIL.
3. 3/8" I.D X 18" GAS FLEX CONNECTORS NOT ADEQUATE
FOR 100,000 BTU
4. SINGLE WALL ELBOW ON FURNACE VENT CONNECTOR UPSIDE DOWN.