Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/04/2007 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* CORRECTIONS HAVE BEEN MADE |
|
| 04/30/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. REMOVE & REPLACE FLATTENED CONDENSATE TRAP. PROVIDE AN OVERFLOW SENSOR ON SECONDARY DRAIN. 2. INSULATE BARE SHEETMETAL SLEEVE ABOVE COIL. 3. 3/8" I.D X 18" GAS FLEX CONNECTORS NOT ADEQUATE FOR 100,000 BTU 4. SINGLE WALL ELBOW ON FURNACE VENT CONNECTOR UPSIDE DOWN. |