Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/08/2006 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* 1) CORRECTIONS OK |
|
| 11/02/2006 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SUPPLY AIR FROM NEW A/C FURN. IS DUCTED INTO EXISTING UNINSULATED EVAP, COOLDER 90 ELBOW. NEED TO INSULATE INTERNALLY OR WRAP AND COVER WITH JACKET 2) NO APPEARANCE OF ANY DAMPER IN SUPPLY DUCT ON COMB. UNIT ?? 3) PVC CONDENSATE PIPING NEEDS TO BE PAINTED. IMPROPER COND. TERMINATION 4) ELECTRIC HIGH VOLTAGE-WIRING OUT OF SWITCH INTO UNIT IS RUNNING IN NEW OPENING. PROVIDE BUSHING AT OPENING AS NECESSARY 4) CORRECT ALL ITEMS, RECALL FOR FINAL |