Permit: T06ME00581

Parcel: 133424690

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
10/11/2006 MECHANICAL - FINAL Approved IVRS - Inspection :*
CORRECTIONS HAVE BEEN MADE.
10/09/2006 MECHANICAL - FINAL Denied IVRS - Inspection :
There is no access to the site.| 920*
CONTR. WILL RECALL WHEN HE CAN COORDINATE ROOF ACCESS FOR INSP.
10/05/2006 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
TERMINATE CONDENSATE WITH A 1" AIR GAP AS WE DISCUSSED. BLOCK & CLAMP PVC EVERY 4'
USE GLUE ON ABS FITTINGS.
10/02/2006 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
SECURE ELEC. DISCONNECT. DO NOT BLOCK SERVICE PANELS.
CONDENSATE CANNOT TERMINATE INTO A SEWER VENT.
CONTROL WIRE MUST BE IN CONDUIT.
GAS FLEX IS NOT TIGHT & IS BACKING GAS.
SHUT OFF VALVE MUST PRECEDE THE FLEX.
DRAIN LINE MUST BE SECURED TO THE BLOCKS.
PERMANENTLY IDENTIFY THE UNIT.
CALL ME TO DISCUSS CONDENSATE ISSUES.