Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/11/2006 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* CORRECTIONS HAVE BEEN MADE. |
|
| 10/09/2006 | MECHANICAL - FINAL | Denied | IVRS - Inspection : There is no access to the site.| 920* CONTR. WILL RECALL WHEN HE CAN COORDINATE ROOF ACCESS FOR INSP. |
|
| 10/05/2006 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* TERMINATE CONDENSATE WITH A 1" AIR GAP AS WE DISCUSSED. BLOCK & CLAMP PVC EVERY 4' USE GLUE ON ABS FITTINGS. |
|
| 10/02/2006 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* SECURE ELEC. DISCONNECT. DO NOT BLOCK SERVICE PANELS. CONDENSATE CANNOT TERMINATE INTO A SEWER VENT. CONTROL WIRE MUST BE IN CONDUIT. GAS FLEX IS NOT TIGHT & IS BACKING GAS. SHUT OFF VALVE MUST PRECEDE THE FLEX. DRAIN LINE MUST BE SECURED TO THE BLOCKS. PERMANENTLY IDENTIFY THE UNIT. CALL ME TO DISCUSS CONDENSATE ISSUES. |