Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/29/2008 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* CORRECTIONS HAVE BEEN MADE |
|
| 02/20/2008 | MECHANICAL - FINAL | Denied | PROVIDE AN OVERFLOW SENSOR ON SECONDARY DRAIN OUTLET ON COIL. CONDENSATE CANNOT TERMINATE INTO A SEWER VENT. SUPPORT EVERY 6'. |