Inspection History: MECHANICAL - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/18/2006 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 12/14/2006 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. 3/8" I.D GAS FLEX NOT ADEQUATE FOR 92,000 BTU. 2. CONDENSATE MUST TERMINATE WITHIN 6" OF THE GROUND 3. PAINT PVC WITH LATEX PAINT 4. BLOCK & CLAMP EVERY 4' 5. TIGHTEN LOOSE ELEC. CONNECTIONS ON AC UNIT & DISCONNECT. 6. INSULATE ALL SHEETMETAL FITTINGS IN THE ATTIC. 7. INSULATION MUST BE MIN. R8 8. IT APPEARS SOME LARGE DUCTS ON THE ROOF ARE NOT INSULATED. 9. MUST USE 2" R8 DUCT LINER ON ALL ROOFTOP DUCTING |