Permit: T06ME00511

Parcel: 12108034A


Addresses:

6171 E BELLEVUE ST

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
11/09/2006 MECHANICAL - FINAL Approved IVRS - Inspection :*
1) CORRECTIONS HAVE BEEN MADE
10/18/2006 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
UNIT 28 IS OK
UNIT 19 IS OK, 25 IS OK
UNIT 31 -- KINKED HOSE, EXPOSED PLASTIC HOSE
UNIT 13 - NEEDS PUMP
UNIT 32 - CONDENSATE TO DOWNSPOUT, BUSHING IN DISCONNECT.
UNIT 33 - LOOSE ELEC. CONNECTION
UNIT 20 - BLOCK & CLAMP DRAIN
UNIT 9 - EXPOSED HOSE
UNIT 6 - CONDENSATE PUMP, BUSHING
10/11/2006 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
CHECK DISCONNECTS FOR CHASE NIPPLES. PROVIDE COVERS OVER CONDENSATE PUMPS. CONDENSATE CANNOT DRIP OUR OF A SCUPPER. BLCOK & CLAMP DRAINS EVERY 4'. TIGHTEN LOOSE ELEC. CONNECTIONS. PROVIDE COVERS OVER CANVAS CONNECTORS AS NEEDED.

UNITS 13, 9, 25 STILL NEED TO BE FIXED.
10/09/2006 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
#31 -- UNIT CONDENSATE DUMPING ON PAVED PARKING LOT
NO ID ON UNIT -- REJECTED

#28 - REJECTED
IMPROPER COND. TERMINATION - NO PAINT ON PVC
NO UNIT #I.D

#20 -- UNABLE TO CK. FUSE SIZE ON #20 - PARTIAL

#19 -- UNABLE TO REMOVE FUSE BLK. FROM SWITCH

OTHER NEW UNITS ARE LOCATED ON THIS ROOF THAT ARE NOT INCLUDED ON THIS INSP. LIST
SUGGEST CONTRACTOR PROVIDE COMPLETE LIST, ADDRESS, ITEMS THAT ARE INCORRECT - A PUNCH LIST IS NOT NECESSARY FOR THIS TYPE JOB.
10/06/2006 MECHANICAL - FINAL Cancelled IVRS - RI canceled