Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/09/2006 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* 1) CORRECTIONS HAVE BEEN MADE |
|
| 10/18/2006 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* UNIT 28 IS OK UNIT 19 IS OK, 25 IS OK UNIT 31 -- KINKED HOSE, EXPOSED PLASTIC HOSE UNIT 13 - NEEDS PUMP UNIT 32 - CONDENSATE TO DOWNSPOUT, BUSHING IN DISCONNECT. UNIT 33 - LOOSE ELEC. CONNECTION UNIT 20 - BLOCK & CLAMP DRAIN UNIT 9 - EXPOSED HOSE UNIT 6 - CONDENSATE PUMP, BUSHING |
|
| 10/11/2006 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* CHECK DISCONNECTS FOR CHASE NIPPLES. PROVIDE COVERS OVER CONDENSATE PUMPS. CONDENSATE CANNOT DRIP OUR OF A SCUPPER. BLCOK & CLAMP DRAINS EVERY 4'. TIGHTEN LOOSE ELEC. CONNECTIONS. PROVIDE COVERS OVER CANVAS CONNECTORS AS NEEDED. UNITS 13, 9, 25 STILL NEED TO BE FIXED. |
|
| 10/09/2006 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* #31 -- UNIT CONDENSATE DUMPING ON PAVED PARKING LOT NO ID ON UNIT -- REJECTED #28 - REJECTED IMPROPER COND. TERMINATION - NO PAINT ON PVC NO UNIT #I.D #20 -- UNABLE TO CK. FUSE SIZE ON #20 - PARTIAL #19 -- UNABLE TO REMOVE FUSE BLK. FROM SWITCH OTHER NEW UNITS ARE LOCATED ON THIS ROOF THAT ARE NOT INCLUDED ON THIS INSP. LIST SUGGEST CONTRACTOR PROVIDE COMPLETE LIST, ADDRESS, ITEMS THAT ARE INCORRECT - A PUNCH LIST IS NOT NECESSARY FOR THIS TYPE JOB. |
|