Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/16/2006 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* CORRECTIONS HAVE BEEN MADE |
|
| 10/19/2006 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* DO NOT USE GREEN WIRE FOR LINE VOLTAGE EVEN IF IT IS TAPED BLACK. BURIED EMT REQUIRED TO BE TAPED. MUST BE MIN. 12" DEEP. LEAVE EXPOSED TO SEE. EXPOSED STAT WIRE MUST BE PROTECTED FROM DAMAGE. PROVIDE A SEDIMENT TRAP IN GAS LINE AT FURNACE. |