Inspection History Details
Inspection Status: Partial Approval
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/22/2006 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* CONDENSATE DRAIN MUST HAVE MIN. 1/8" PER FT. SLOPE THE ENTIRE WAY WITH NO UPHILL RUNS. BLOCK & CLAMPS DRAIN LINE EVERY 4' RECALL FOR INSPECTION. |