Permit: T06ME00461

Parcel: 13005039B

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
09/28/2006 MECHANICAL - FINAL Approved IVRS - Inspection :*
09/12/2006 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
PROGRESSING
1. FURN. RM. DUCTS (FLEX) IN CONTACT WITH B-1 VENT PIPE.
NEED CLEARANCE AS NECESSARY.
2. COMBUSTION/RELIEF AIR?
3. EAST SIDE UNIT, CONNECT/CORRECT ELEC. HI VOLTAGE CIR. INTO SWITCH, PROVIDE PROPER ACCESS.
08/17/2006 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
- GAS FLEX TO FURNACE CANNOT EXCEED 3' IN LENGTH & - CANNOT PENETRATE ANY PARTITION.
- CAP OFF UNUSED GAS LINE UNDER THE PLATFORM.
- CONNECT OVERFLOW SENSOR ON CONDENSATE PUMP. - PROVIDE A HOSE CLAMP ON PUMP.
- PROVIDE A TRAP ON DRAIN LINE AS PER INSTALL INSTRUCTIONS.
- PROVIDE 4" DOUBLE WALL VENT PIPE ON FURNACE & REDUCE TO 3" AT FURNACE.
- TERMINATE WITH AN APPROVED ROOF JACK & CAP
- DO NOT USE SHIPPING CRATES TO SUPPORT CONDENSORS
- USE REDWOOD SLEEPERS & LEVEL CONDENSORS
- CONDENSATE CANNOT DRAIN ONTO THE ROOF.
- EXPOSED STAT WIRE MUST BE IN A CONDUIT.