Permit: T06ME00451

Parcel: 112040580

Inspection Status: Partial Approval

Inspection History: MECHANICAL - FINAL

Permit Number - T06ME00451

Inspection Description - MECHANICAL - FINAL

Inspection Status - Partial Approval

Date Description Inspector Results Comments
08/14/2006 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1. NEED PERMIT FOR ELECT. CIRCUIT, SERVICE UP TO NEW UNIT LOCATION.
2. IMPROPER CONDENSATE TERMINATION - PVC PLASTIC NEEDS TO BE PAINTED. UNIT DOUBLE TAPED???
3. I.D CIR. BKR. IN ELECT. SERVICE ENTRANCE FOR A/C
4. CONTROL WIRING ON ROOF EXPOSED TO SUN
5. FUSING ON ROOF INCORRECTLY SIZED.
6. SEAL SUPPLY/RETURN ELLS TO ROOF FLASHINGS AT ROOF.