Inspection History Details
Inspection Status: Partial Approval
Inspection History: MECHANICAL - FINAL
Permit Number - T06ME00451
Inspection Description - MECHANICAL - FINAL
Inspection Status - Partial Approval
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/14/2006 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1. NEED PERMIT FOR ELECT. CIRCUIT, SERVICE UP TO NEW UNIT LOCATION. 2. IMPROPER CONDENSATE TERMINATION - PVC PLASTIC NEEDS TO BE PAINTED. UNIT DOUBLE TAPED??? 3. I.D CIR. BKR. IN ELECT. SERVICE ENTRANCE FOR A/C 4. CONTROL WIRING ON ROOF EXPOSED TO SUN 5. FUSING ON ROOF INCORRECTLY SIZED. 6. SEAL SUPPLY/RETURN ELLS TO ROOF FLASHINGS AT ROOF. |