Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/03/2009 | MECHANICAL - FINAL | Approved | ELECTRIC UPGRADE # T06EL01758 | |
| 08/24/2006 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* ALL MECHANICAL CORRECTIONS HAVE BEEN MADE. HOWEVER, THERE IS STILL NO ELEC. UPGRADE PERMIT. THIS COULD BECOME A PROBLEM IF YOU HAD TO SELL YOUR HOUSE OR NEEDED A PERMIT FOR SOMETHING ELSE. |
|
| 08/11/2006 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* CHANGE GAS FLEX CONNECTOR AS NOTED ON PREVIOUS INSPECTION. PROVIDE A PERMIT FOR THE ELEC. PANEL UPGRADE |
|
| 07/31/2006 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* - NEED TO SEE WHERE GAS LINE TO FURNACE IS CONNECTED. - 3/8" I.D X 24" GAS FLEX NOT ADEQUATE FOR 120,000 BTU FURNACE. - NEED TO SEE CIRCUIT BREAKER. - CONDENSATE MUST TERMINATE TO WITHIN 6" OF THE GROUND. BLOCK & CLAMP DRAIN LINE. - NEED TO SEE ALL NEW DUCTING IN ATTIC. - PROPERLY ABANDON OLD EVAP. COOLER ELEC. CIRCUIT - PROVIDE A BUSHING IN ELEC. DISCONNECT TO A/C UNIT. |