Permit: T06ME00414

Parcel: 11449031H

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
10/24/2006 MECHANICAL - FINAL Approved IVRS - Inspection :*
08/01/2006 MECHANICAL - FINAL Denied IVRS - Inspection :
A reinspection fee has been assessed for this inspection. Multiple inspectio
ELEC. CONDUIT STILL NOT BLOCKED & CLAMPED AS NOTED ON PREVIOUS INSPECTION.
CONDENSATE CANNOT TERMINATE INTO A HOLE DRILLED INTO A SEWER VENT.
TERMINATE TO WITHIN 6" OF THE GROUND AS NOTED ON PREVIOUS INSPECTION.
PAY A REINSPECTION FEE PRIOR TO NEXT INSPECTION.
07/28/2006 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
ELEC. DISCONNECT OVERFUSED
CONDENSATE CANNOT DRIP OUT OF THE SCUPPER.
MUST GO TO WITHIN 6" OF THE GROUND.
BLOCK & CLAMP ELEC. CONDUIT
PAINT ALL EXPOSED PVC W/LATEX PAINT.