Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/17/2006 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* CORRECTIONS HAVE BEEN MADE |
|
| 09/20/2006 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* - CONDENSATE CANNOT TERMINATE INTO A SEWER VENT. - PAINT EXPOSED PVC W/LATEX PAINT. - VENT MUST BE DOWNSTREAM OF THE TRAP. - PROVIDE A PRESSURE TEST ON ALL NEW GAS PIPING. - RELOCATE ELEC. DISCONNECT TO ALLOW CLEARANCE FOR SERVICE. - SUPPORT AND SECURE ELEC. CONDUITS. |