Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T06ME00279
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/15/2010 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
10/04/2010 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) #8 WIRE OK FOR MINIMUM 47.3 AMPS 2) LOW VOLTAGE WIRE CANNOT BE INSTALLED IN A CONDUIT WITH HIGH VOLTAGE WIRES 3) SUPPORT EXPOSED PVC EVERY 4' |
|
05/25/2006 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. WHERE WAS SOUCE OF GAS GOINT TO NEW ROOF TOP COMB. UNIT. 2. ELECT. CIRCUIT -- PANEL TO ROOF TOP. A. NO.#8 WIRE - GOOD FOR 50 AMPS. MAX. B. UNIT FUSED AT 60 - REFUSE AT 50 OR INCREASE WIRE TO #6 3. CONDENSATE PIPING - A. UNIT NEEDS TRAP B. TERMINATE AT GUTTER W/DOWN SPOUT NO ROOF DRAINS (SEWER WASTES) ALLOWED. C. PAINT PVC PIPING. 4. REMOVE 24 VOLT WIRING FROM HIGH VOLTAGE CIRCUITRY. RUN CONTROL WIRE IN EMT OR FLEX. BRACE HIGH VOLTAGE SWITCH. |