Permit: T06ME00273

Parcel: 133420650

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
10/03/2006 MECHANICAL - FINAL Approved IVRS - Inspection :*
CORRECTIONS HAVE BEEN MADE
09/20/2006 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
- CONDENSATE CANNOT DRAIN INTO THE PARKING LOT.
- YOU CAN USE A CONDENSATE PUMP & TERMINATE 3/8" COPPER TUBING OVER THE TOP OF A SEWER VENT.
- MECHANICAL CONTRACTOR CALL ME TO DISCUSS OPTIONS.
JIM 909-4712
09/18/2006 MECHANICAL - FINAL Denied IVRS - Inspection :
There is no access to the site.| 920*
CALLED -- LEFT MESSAGE
NEED ACCESS TO ROOF TO CHECK CORRECTIONS
SORRY I MISSED YOU
09/08/2006 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
CONDENSATE CANNOT TERMINATE INTO A SEWER VENT.
SECURE THE ELEC. DISCONNECT. A/C UNIT NOT FUSED CORRECTLY. TIGHTEN LOOSE ELEC. CONNECTIONS.
LOW VOLTAGE WIRE MUST BE IN CONDUIT.
PERMANENTLY IDENTIFY THE A/C UNIT.