Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/03/2006 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* CORRECTIONS HAVE BEEN MADE |
|
| 09/20/2006 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* - CONDENSATE CANNOT DRAIN INTO THE PARKING LOT. - YOU CAN USE A CONDENSATE PUMP & TERMINATE 3/8" COPPER TUBING OVER THE TOP OF A SEWER VENT. - MECHANICAL CONTRACTOR CALL ME TO DISCUSS OPTIONS. JIM 909-4712 |
|
| 09/18/2006 | MECHANICAL - FINAL | Denied | IVRS - Inspection : There is no access to the site.| 920* CALLED -- LEFT MESSAGE NEED ACCESS TO ROOF TO CHECK CORRECTIONS SORRY I MISSED YOU |
|
| 09/08/2006 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* CONDENSATE CANNOT TERMINATE INTO A SEWER VENT. SECURE THE ELEC. DISCONNECT. A/C UNIT NOT FUSED CORRECTLY. TIGHTEN LOOSE ELEC. CONNECTIONS. LOW VOLTAGE WIRE MUST BE IN CONDUIT. PERMANENTLY IDENTIFY THE A/C UNIT. |