Permit: T06ME00237

Parcel: 137292790


Addresses:

1831 W DEACON DR

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
05/18/2006 MECHANICAL - FINAL Approved IVRS - Inspection :*
05/17/2006 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
ALUMINUM CONDUCTORS ON THE LOAD SIDE OF DISCONNECT 60 AMP. REQUIRES #4 WIRE.
PROVIDE ROOF JACKS AT ALL ROOF PENETRATIONS.
USE THE PROPER SIZE FITTING TO CONNECT SEAL
TITE TO UNIT.
VENT ON CONDENSATE MUST BE DOWNSTREAM OF THE TRAP.
SECURE PVC TO WALL AT TERMINATION.
NEED TO SEE CIRCUIT BREAKER.
05/10/2006 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1. ELECT SWITCH ROMEX CONNECTOR IN HOLE AT REAR OF SWITCH.
2. FUSE AT 60 AMPS. - #6 WIRE
ELECT. 60 AMP. BKRS.
3. CONDENSATE, PVC, PLASTIC RUN DOWN TO DIRT BLOCKS EVERY 4 FT.