Inspection History: MECHANICAL - FINAL
Permit Number - T06ME00219
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/05/2010 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 01/20/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CONDENSATE CANNOT TERMINATE INTO A SEWER VENT 2) EXTEND SEWER VENT MINIMUM 2' ABOVE FRESH AIR INTAKE ON SMALL UNIT 3) LOWER FRESH AIR INTAKES MINIMUM 2' BELOW EXHAUST FAN 4) PROVIDE A FULL LENGTH SLEEPER AT FRONT OF LARGE UNIT 5) SLOPE CONDENSATE DRAINS MINIMUM 1/8" PER FT AND PAINT WITH LATEX PAINT 6) LARGE UNIT IS OVERFUSED 7) PROVIDE A PLUG IN THE OPEN KNOCKOUT IN DISCONNECT FOR SMALL UNIT 8) PROVIDE A PROTECTIVE COATING ON WATER LINE INSULATION ON ROOF AND CLAMP TO BLOCKS |
|
| 12/21/2009 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 12/10/2009 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ALL DUCT JOINTS AND SEAMS ARE TO BE SEALED WITH HARDCAST OR CMC SEALER 2) ALL FLEX CONNECTORS EXPOSED TO SUNLIGHT ARE TO HAVE SUN SHIELDS 3) ALL DUCT EXPOSED TO THE EXTERIOR SHALL HAVE R-8 (2") INSULATION 4) CONDENSATE IS TO TERMINATE AT AN APPROVED LOCATION (CANNOT TERMINATE AT WASTE VENT) 5) T-STAT WIRE TO BE IN CONDUIT 6) PROVIDE OUTSIDE AIR INLET AND BALANCE PER I.E.C.C. 7) FILTERS NOT PROPERLY INSTALLED OR NOT PRESENT 8) FILTER DOOR DOES NOT PROPERLY FIT INTO OPENING 9) UNIT DATA PLATES NOT PROPERLY IDENTIFIED (HEAT STRIPS) UNABLE TO DETERMINE CORRECT FUSE SIZE 10) T-STAT WIRE TO BE BLOCKED 1.5" MINIMUM FROM ROOF |