Permit: T06ME00218

Parcel: 123060160


Addresses:

2001 E LEE ST

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
05/16/2006 MECHANICAL - FINAL Approved IVRS - Inspection :*
FURNACE & REMOTE A/C CONDENSER
05/12/2006 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1. INSULATE SUCTION LINE AT EVAPORATOR COIL.
2. INSULATE ALL SUPPLY/RETURN DUCTING IN CRAWL SPACE, FURN. RM. ETC.
3. ISOLATE ALL STEEL CLAMPS FROM REGRIG. COPPER PIPING.
4. NEED TO TERMINATE B-1 VENT W/PROPER CAP ON ROOF.