Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/04/2006 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 04/03/2006 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* | |
| 03/31/2006 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. IMPROPER CONDENSATE TERMINATION PVC REQUIRES COAT OF LATEX PAINT. 2. GAS LINE, WEST SIDE OF UNIT IS BLOCKING ACCESS PANEL TO FURNACE SECTION. REPIPE, LEAVE CLEAR ACCESS TO PANEL FOR SERVICE. 3. ELECT. CIRCUIT WIRING TO SMALL, CIR. BKR. IN PANEL TO BIG. |
|
| 03/24/2006 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* ROOFERS REPLACING ROOF - UNIT NOT READY FOR INSP. WILL DO FINAL ON RE-INSPECTION AFTER ROOFING COMPLETED AND UNIT WITH ALL UTILITIES ARE IN FINAL POSITION. |