Permit: T06ME00118

Parcel: 125031560


Addresses:

3070 E 4TH ST

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
03/29/2006 MECHANICAL - FINAL Approved IVRS - Inspection :*
CORRECTIONS HAVE BEEN MADE
03/17/2006 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
BOTH UNITS TERMINATE CONDENSATE INTO DOWNSPOUTS
UPPER UNIT OVERFUSED. SECURE ELEC.
DISCONNECT
RECALL FOR INSPECTION.