Inspection History Details
Inspection Status: Denied
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/13/2006 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) 240 VOLT UNIT WITH 9.6 KW HEAT STRIP REQUIRES 80 AMP FUSES, CIRCUIT BREAKER AND WIRING |