Permit: T06ME00076

Parcel: 121060840


Addresses:

5631 E MABEL ST


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T06ME00076

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/02/2007 MECHANICAL - FINAL Approved IVRS - Inspection :*
06/11/2007 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. FAILED GAS PRESSURE TEST ON ROOF. REPAIR ANY LEAKS AND RETEST. TRY DIFFERENT GAUGE...IT SHOULD READ IN 1/10 LB INCREMENTS.
12/13/2006 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. NEED TO SEE WHERE NEW GAS PIPE IS CONNECTED
2. PROVIDE A PRESSURE TEST ON ALL NEW GAS PIPE.
3. I CANNOT CONFIRM THE GAS PIPE IS LISTED WITH PAINT ALL OVER IT.
4. REPLACE OR REMOVE PAINT & EXPOSE LETTERING ON PIPE.
5. PROVIDE AN ELBOW ON END OF CONDENSATE DRAIN & AN END CAP ON RAIN GUTTER.
6. PAINT EXPOSED PVC W/LATEX PAINT
7. PROVIDE A ROOF JACK AT ELEC. PENETRATION THRU THE ROOF.