Permit: T06ME00072

Parcel: 135060390

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
02/21/2006 MECHANICAL - FINAL Approved IVRS - Inspection :*
02/17/2006 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
PROVIDE A TEST GAUGE THAT ACTUALLY WORKS W/MIN 10 LB. PRESSURE
02/16/2006 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999* CONDENSATE CANNOT TERMINATE INTO A SEWER VENT. VENT ON CONDENSATE DRAIN M UST BE DOWNSTREAM OF THE TRAP. PROVIDE A MIN 10 LBS PRESSURE TEST ON AL NEW GAS PIPING. 3/8" I.D GAS FLEX 18" LONG NOT ADEQUATE FOR 98,000 BTU
DO NOT USE WHITE WIRE FOR HIGH VOLTAGE TAPE ENDS BLACK IN DISCONNECT & CIRCUIT PANEL