Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/21/2006 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 02/17/2006 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* PROVIDE A TEST GAUGE THAT ACTUALLY WORKS W/MIN 10 LB. PRESSURE |
|
| 02/16/2006 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* CONDENSATE CANNOT TERMINATE INTO A SEWER VENT. VENT ON CONDENSATE DRAIN M UST BE DOWNSTREAM OF THE TRAP. PROVIDE A MIN 10 LBS PRESSURE TEST ON AL NEW GAS PIPING. 3/8" I.D GAS FLEX 18" LONG NOT ADEQUATE FOR 98,000 BTU DO NOT USE WHITE WIRE FOR HIGH VOLTAGE TAPE ENDS BLACK IN DISCONNECT & CIRCUIT PANEL |