Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/14/2006 | MECHANICAL - FINAL | Approved | IVRS - Inspection :*CORRECTIONS HAVE BEEN MADE | |
| 02/06/2006 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 01/31/2006 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* GAS PIPE USED DOES NOT HAVE A LISTING OR LABEL ON THE PIPE. MUST USE ASTM A53. GAS SHUT OFF VALVE MUST BE AHEAD OF THE GAS FLEX. BLOCK & CLAMP GAS PIPING. - LOW VOTTAGE WIRE MUST BE IN CONDUIT AS PER N.E.C - PROVIDE A CONDENSATE DRAIN TO AN APPROVED LOCATION - BLOCK & CLAMP ELEC. CONDUIT ON ROOF - INSULATE EXPOSED DUCT WORK ON ROOF WITH MIN. 2" R8 DUCT LINE. - FRONT OF UNIT MUST BE ON THE STAND OR PROVIDE A REDWOOD SLEEPER. |