Permit: T06ME00040

Parcel: 126030220


Addresses:

749 N BENTON AV

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
02/14/2006 MECHANICAL - FINAL Approved IVRS - Inspection :*CORRECTIONS HAVE BEEN MADE
02/06/2006 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
01/31/2006 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
GAS PIPE USED DOES NOT HAVE A LISTING OR LABEL ON THE PIPE. MUST USE ASTM A53. GAS SHUT OFF VALVE MUST BE AHEAD OF THE GAS FLEX. BLOCK & CLAMP GAS PIPING.
- LOW VOTTAGE WIRE MUST BE IN CONDUIT AS PER N.E.C
- PROVIDE A CONDENSATE DRAIN TO AN APPROVED LOCATION
- BLOCK & CLAMP ELEC. CONDUIT ON ROOF
- INSULATE EXPOSED DUCT WORK ON ROOF WITH MIN. 2" R8 DUCT LINE.
- FRONT OF UNIT MUST BE ON THE STAND OR PROVIDE A REDWOOD SLEEPER.