Case: T06FR02928

Parcel: 14027046C


Addresses:

2640 E GANLEY RD

Inspection Status: Approved

Inspection History: INSP - AST/UST

Date Description Inspector Results Comments
01/12/2007 INSP - AST/UST Approved Corrected
12/26/2006 INSP - AST/UST Correction Required 3807.4 Protecting containers from vehicles. Where exposed to vehicular damage due to proximity to alleys, driveways or parking areas, LP-gas containers, regulators and piping shall be protected in accordance with Section 312.

3808.2 Fire extinguishers. Fire extinguishers complying with Section 906 shall be provided as specified in NFPA 58. Fire extinguisher type 2A20BC rating shall be provided at a distance of not less than 10 feet but no more than 50 feet from the container and shall be properly mounted.