Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/23/2007 | INSP - FULL | Approved | Final inspection. | |
| 12/20/2006 | INSP - FULL | Violation | 2003 IFC-105.3 Certificate of Occupancy shall be posted. 2003 IFC-3003.3.3 Comprress gas cylinders shall be secured to prevent falling. 2003 IFC-605.5 Extension cords shall not be a substitute for permanent wiring. 2003 IFC-904.11.6.3 The hood system duct works from the ceiling down to the ducts shall be free of grease. 2003 904 The hood fire sprinkler system is due this month. |