Case: T06FR02893

Parcel: 137105050


Addresses:

5550 S 12TH AV #108

Inspection Status: Violation

Inspection History: VIOL - MEANS OF EGRESS

Date Description Inspector Results Comments
12/15/2006 VIOL - MEANS OF EGRESS Violation 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. Remove the double key locking cylinder on rear exit door and replace with a thumb latch bolt on the egress side.
12/15/2006 VIOL - MEANS OF EGRESS Violation 1011.2 Illumination. Exit signs shall be internally or externally
illuminated. Ensure proper illumination of both exit signs.