Case: T06FR02864

Parcel: 10408053K


Addresses:

4525 N ORACLE RD

Inspection Status: Approved

Inspection History: INSP - FULL

Date Description Inspector Results Comments
02/08/2007 INSP - FULL Approved
02/08/2007 INSP - FULL Approved
02/08/2007 INSP - FULL Approved
02/08/2007 INSP - FULL Approved
02/08/2007 INSP - FULL Approved
12/12/2006 INSP - FULL Violation 2003 IFC 901.6 REPLACE BROKEN FD CAP ON EAST SIDE OF BUILDING.
12/12/2006 INSP - FULL Violation 2003 IFC 1026.3 THE 2 OUTSIDE EXIT SIGNS IN THE COVERED ENTRANCE MUST BE LIT.
12/12/2006 INSP - FULL Violation 2003 IFC 703.1 REPLACE CEILING TILE IN STORAGE ROOM ABOVE HOT WATER HEATER.
12/12/2006 INSP - FULL Violation 2003 IFC 304.1.1 REMOVE EXCESS TRASH ON THE WEST SIDE OF STORE BY THE DUMPSTER.
12/12/2006 INSP - FULL Violation 2003 IFC 605.1 BLANKS SHALL BE INSTALLED IN PLACE OF MISSING BREAKERS ON "HD" PANEL WEST SIDE OF ELECTRICAL ROOM.
12/12/2006 INSP - FULL Violation 2003 IFC 2305.4 ONE-HALF OF THE ISLE WIDTH SHALL REMAIN CLEAR WHEN RE-STOCKING.
12/12/2006 INSP - FULL Violation 2003 IFC 1013.4.1 AISLES IN SECURITY BOOTH STOCKING RM (EAST SIDE) SHALL BE MAINTAINED A MINIMUM OF 28 INCHES.