Case: T06FR02861

Parcel: 134252060


Addresses:

7056 E 21ST ST

Inspection Status: Correction Required

Inspection History: INSP - FULL

Date Description Inspector Results Comments
12/12/2006 INSP - FULL Correction Required FIRE INSPECTION REPORT


12/01/06

Ace Hardware Warehouse
ATTN: Harry Findysz
7056 E 21nd St.
Tucson, AZ. 85710







Mr. Findysz,

The Tucson Fire Department has conducted a fire safety inspection at the above stated business on December 12, 2006. Below is a list of violations that shall be corrected to provide compliance with the applicable codes, regulations and ordinances. Compliance is required by the 2003 International Fire Code with modifications. A Re-inspection will be performed on or about January 2, 2007.


Violations:
605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes.
1. Power cord along ceiling

1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort.
1. Do not hinder the operation on South exit

605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances.
1. Remove the cord under the desk in the Southwest portion of the warehouse.




315.2.1 Ceiling clearance. Storage shall be maintained 2 feet (610 mm) or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches (457 mm) below sprinkler head deflectors in sprinklered areas of buildings.
1. Stock shall not come with 18 inches of sprinkler heads: above the rooms.


605.4 Multiplug adapters. Multiplug adaptors, such as cube adaptors, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited.
1. Time clock


315.2 Storage in buildings. Storage of combustible materials in buildings shall be orderly. Storage shall be separated from heaters or heating devices by distance or shielding so that ignition cannot occur.
1. The storage of your cooler pad shall be orderly and an aisle of 24 inches provided to break up the fuel.


The Tucson Fire Department is committed to the protection of your property. Your help as a business owner and as a citizen is greatly appreciated.

__________________________________________________
Property owner or Property Representative Signature
_________________________________
Abatement Date
__________________________
Captain Signature


Sincerely,


Jimmy R. Davis, Jr.
Fire Inspector
Tucson Fire Department
797 E. Ajo
Tucson, AZ 85713-5011
(520) 791-4502 fire prevention center