Inspection Status: Approved
Inspection History: VIOL - MEANS OF EGRESS
Case Number - T06FR02859
Inspection Description - VIOL - MEANS OF EGRESS
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/19/2007 | VIOL - MEANS OF EGRESS | Approved | Emergency lighting fixed, fully operational | |
| 12/29/2006 | VIOL - MEANS OF EGRESS | Approved | New exit signs installed, fully functional. | |
| 12/29/2006 | VIOL - MEANS OF EGRESS | Correction Required | New battery installed, however, unit never tested. Still inoperative, return in two weeks, or when light is repaired, whichever is first. | |
| 12/11/2006 | VIOL - MEANS OF EGRESS | Violation | 5. Exit sign illumination. Exit signs shall be externally or internally illuminated.IFC 2003-1026.3 ***Repair Exit sign. |
|
| 12/11/2006 | VIOL - MEANS OF EGRESS | Violation | 6. Emergency lighting. Emergency lighting on south wall is inoperative. In the event of power supply failure, an emergency system shall automatically illuminate exit corridors. IFC 2003-1006.3 ***Repair Emergency lighting. |