Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - PRECAUTION AGAINST FIRE
Case Number - T06FR02859
Inspection Description - VIOL - PRECAUTION AGAINST FIRE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/29/2006 | VIOL - PRECAUTION AGAINST FIRE | Approved | All storage around heater removed with appropriate space around heater. | |
| 12/29/2006 | VIOL - PRECAUTION AGAINST FIRE | Approved | Storage within limits. | |
| 12/11/2006 | VIOL - PRECAUTION AGAINST FIRE | Violation | 3. Combustible storage around hot water heater. Storage of combustible materials shall be separated from heaters and heating devices by distance or shielding so that ignition cannot occur. IFC 2003-315.2 ***Clear storage from water heater area. |
|
| 12/11/2006 | VIOL - PRECAUTION AGAINST FIRE | Violation | 4. Ceiling clearance. Storage shall be maintained 2ft. (610mm) or more below the ceiling in non-sprinklered areas of a building. IFC 2003-315.2.1 ***keep storage within limits. |